Civil Defence Measures

dcdfs54Fire Stations
4Emirates Martyrs Station
Date of Establishment
Area of Jurisdication
Contact Us
360 Photo-DCD
4Karama Station
Date of Establishment
Area of Jurisdication
Contact Us
360 Photo-DCD
4Al Barsha Station
Date of Establishment
Area of Jurisdication
Contact Us
360 Photo-DCD
4Port Saeed Station
Date of Establishment
Area of Jurisdication
Contact Us
360 Photo-DCD
4Al Marsa Station
Date of Establishment
Area of Jurisdication
Contact Us
360 Photo-DCD
4Al Qusais Station
Date of Establishment
Area of Jurisdication
Contact Us
360 Photo-DCD
4Al Hamriya Station
Date of Establishment
Area of Jurisdication
Contact Us
360 Photo-DCD
4Al Ras Station
Date of Establishment
Area of Jurisdication
Contact Us
360 Photo-DCD
4Al Qouz Station
Date of Establishment
Area of Jurisdication
Contact Us
360 Photo-DCD
4Al Rashidya Station
Date of Establishment
Area of Jurisdication
Contact Us
360 Photo-DCD
4Al Satwa Station
Date of Establishment
Area of Jurisdication
Contact Us
360 Photo-DCD
4Al Lasaili Station
Date of Establishment
Area of Jurisdication
Contact Us
360 Photo-DCD
2Jebel Ali Station
Contact Us
360 Photo-DCD
4Hatta Station
Date of Establishment
Area of Jurisdication
Contact Us
360 Photo-DCD
dcd-companies-listCompanies
preventive-safety-dept15Preventive Safety
5Rules & Regulations
UAE Fire and Life Safety Code of Practice
Annexure A.1.21. Fire Stopping and Exterior Cladding
Annexure B1. Balcony, Terrace, Windows
Annexure B2. Emergency Action Plans
FAQ - UAE Fire and Life Safety Code of Practice
4Project / Drawing Approval Req
E-Engineering User Manual
3Sample E-engineering Checklist
Business Highrise
Healthcare Highrise
Mercantile Décor
Consultants-Drawing Submission Requirements
Décor - Drawing Submission Requirements
LPG Drawing Submission Requirements
DCD Approved International Testing & Certification Bodies
New Forms
Reasons for Return
newslettersNewsletters
2015-08-05-09-03-1012Our Department
4Fire & Rescue
Fire Stations Department
Department of Operations
Technical Affairs
Marine Fire & Rescue
2Safety & Protection Affairs
Preventive Safety
Civil Protection
4Resources & Support Services
Human Resources
Financial
Communications & Electronic
Services & Supplies
Office & Monitoring
Strategy & Performance
smarts2Smart Services
DCD Smart Services
General Smart Services
dcdss247Smart System (24x7)
faq-sFaq's
dcdorOur Regulations
stipsSafety Tips
dcd-our-policiesOur Policies
strategic-plan-2014-162Strategic Plan
Strategic Plan 2014-16
Stratetic Objective
2016-02-24-11-46-33Services Guidelines

Faq's

  • Q1. What is the fire rating for building having more than 2 basements?

    A1.   All structural members up to and including the floor of the lowest level of discharge of underground buildings more than 7000 mm below or more than two level below the lowest level of exit discharge (i.e. All High depth Underground Buildings or Structures) shall be at least 2 hours fire rated construction.

    Hits :  611
  • Q2. What is the definition of a high-rise building or structure?

    A2.   The occupancies or Multiple and Mixed occupancies, facilities, buildings and structures having  total height of occupiable or usable space of more than 23 Meters above the lowest grade or lowest level of Fire Service Access into that occupancy is categorized as Highrise Building.

    Hits :  2031
  • Q3. What is the definition of a midrise building or structure?

    A3.   The occupancies or Multiple and Mixed occupancies, facilities, buildings and structures having total height of occupiable or usable space between 15 Meters to 23 Meters from the lowest grade or lowest level of Fire Service Access into that occupancy is categorized as Midrise Building.

    Hits :  1195
  • Q4. What is the definition of a low-rise building or structure?

    A4.   The occupancies or Multiple and Mixed occupancies, facilities, buildings and structures having total height of occupiable or usable space up to 15 Meters from the lowest grade or lowest level of Fire Service Access into that occupancy is categorized as Low-rise Building.

    Hits :  1055
  • Q5. What is the definition of a low depth structure or building?

    A5.   A structure or a building with up to two basements or up to 7 m below the level of exit discharge.

    Hits :  825
  • Q6. What is the definition of a high depth structure or building?

    A6.   A structure or a building with more than two basements or more than 7 m below the level of exit discharge.

    Hits :  669
  • Q7. Fire rating and the minimum size of the Emergency Command Centre?

    A7.   The Emergency command centre shall be separated from other parts of the same building by compartment walls and floors having fire resistance of at least 1 hour with fire suppression system. Minimum size shall be 8.9 m².

    Hits :  990
  • Q8. At what level shall the fire pump be installed within the building?

    A8.   Fire pumps shall be located on the ground floor or below grade level with protected dedicated access from the fire engine access level.  

    Hits :  1080
  • Q9. what shall the intermediate fire pumps and water tanks be located for high-rise builds?

    A9.   Where multiple pump sets are required in a Highrise building, Intermediate Fire Pumps and Water tanks shall be located at not more than 90 m intervals from the First Fire Pump located at the lowest level of the structure.

    Hits :  848
  • Q10. When can the separation between the kitchen and the dining area be exempted?

    A10.   Separation requirement for kitchen could be exempted when all the cooking facilities in the kitchen are fitted with an approved extinguishing system such as Kitchen hood suppression. Separation requirement for kitchen could also be exempted when an eating establishment is separated from other parts of the same building by walls and floors having fire resistance of at least 1 hour and doors having fire resistance of at least half an hour.

    Hits :  705
  • Q11. What is the maximum size of a kitchen allowed in a non-sprinklered building?

    A11.   For a non-sprinkler protected building, the floor area of the kitchen compartment shall not exceed 150 m².

    Hits :  681
  • Q12. What is the fire rating for the separation between theatre, cinema or concert hall from other parts of the building?

    A12.   A theater, cinema or concert hall shall be separated from other parts of the same building, which is of a different purpose group, by compartment walls and floors having a fire resistance of at least 2-hour. If the building is protected by an automatic sprinkler system, the fire resistance rating of the compartment walls or floors can be reduced to 1-hour.

    Hits :  513
  • Q11. What is the maximum size of a kitchen allowed in a non-sprinklered building?

    A11.   For a non-sprinkler protected building, the floor area of the kitchen compartment shall not exceed 150 m².

    Hits :  583
  • Q12. What is the fire rating for the separation between theatre, cinema or concert hall from other parts of the building?

    A12.   A theater, cinema or concert hall shall be separated from other parts of the same building, which is of a different purpose group, by compartment walls and floors having a fire resistance of at least 2-hour. If the building is protected by an automatic sprinkler system, the fire resistance rating of the compartment walls or floors can be reduced to 1-hour.

    Hits :  348
  • Q13. What is the fire rating for hotel bedrooms?

    A13.   Each hotel bedroom shall be compartmented from adjoining rooms and other parts of the same building by construction having fire resistance rating of at least 1 hour.

    Hits :  934
  • Q14. What is the fire rating for labor accommodation bedroom?

    A14.   Each labor accommodation bedroom shall be compartmented from adjoining rooms and other parts of the same building by construction having fire resistance rating of at least 1hour.

    Hits :  743
  • Q15. What are the kitchen fire rating requirements for a labor accommodation?

    A15.   Kitchens are only allowed on the ground floor and shall be enclosed with minimum 1-hour fire rated compartment wall, including ½-hour fire rated door. Kitchen shall be separated by 1 hour fire rating and a protected corridor away from the dormitory sleeping area on the ground floor.  

    Hits :  619
  • Q16. What is the fire rating required for motor vehicle workshop?

    A16.   A motor vehicle workshop shall be separated from any other part of the same building by compartment walls and floors having fire resistance of not less than 2 hours.

    Hits :  533
  • Q17. What is the fire rating and ventilation requirement for a spray painting booth or for any spray painting process?

    A17.   Areas in which spray painting or other allied processes are performed or carried out, shall be separated from other parts of the same building by compartment walls and floors having fire resistance of not less than 2 hours. Spray painting booths shall have built in vapor extraction system.

    Hits :  557
  • Q18. What is the size requirement for cold room and the fire rating of the construction?

    A18.   Where a cold room has a floor area exceeding 20 m², a separate outer layer of noncombustible construction, including the door, having minimum 1-hour fire resistance rating (with sprinkler), shall be provided to compartmentalize the cold room enclosure from other areas. Provision of the fire resisting outer layer enclosure, including the fire door to the cold room would not be required if the cold room has a floor area not exceeding 20 m² and is sprinkler protected. The storage materials shall not include highly flammable chemicals. Cold room lesser than 20 m² provided with at least one hour fire rating compartment, need not be provided with sprinklers provided that the storage shall not include flammable materials.

    Hits :  743